Abstract
SMACNA’s Technical Resources Committee, with the guidance of the Architectural Sheet Metal Committee, conducted wind testing of custom-fabricated gravel stop fascia and coping designs shown within the SMACNA Architectural Sheet Metal Manual. This testing was done to provide the design community documentation that proved custom sheet metal met the wind design standards. This test data can be used by designers to determine the site- and building-specific requirements for wind uplift and pull-off.
SMACNA’s Technical Resources Committee, with the guidance of the Architectural Sheet Metal Committee, conducted wind testing of custom-fabricated gravel stop fascia and coping designs shown within the SMACNA Architectural Sheet Metal Manual. This testing was done to provide the design community documentation that proved custom sheet metal met the wind design standards. This test data can be used by designers to determine the site- and building-specific requirements for wind uplift and pull-off.